Energy Savings with invertersif you have an AC motor-driven application that does not need to be run at full speed, then you can cut down energy costs by controlling the motor with an inverter (frequency inverter, aka variable frequency drive). Inverters allow you to match the speed of the motor-driven equipment to the process requirement. There is no other method of AC motor control that allows you to accomplish this.
Example of an Excellent inverter Candidate
Example of a Decent inverter Candidate
Example of a Poor inverter Candidate
Variable Torque Versus Constant Torque
Inverters, and the loads they are applied to, can generally be divided into two groups: constant torque and variable torque. The energy savings potential of variable torque applications is much greater than that of constant torque applications. Variable torque loads include centrifugal pumps and fans, which make up the majority of HVAC applications. Constant torque loads include vibrating conveyors, punch presses, rock crushers, machine tools, and other applications where the inverter follows a constant V/Hz ratio.
Why Variable Torque Loads Offer Great Energy Savings
in variable torque applications, the torque required varies with the square of the speed, and the horsepower required varies with the cube of the speed, resulting in a large reduction of horsepower for even a small reduction in speed. The motor will consume only 25% as much energy at 50% speed than it will at 100% speed. This is referred to as the Affinity Laws, which define the relationships between speed, flow, torque, and horsepower. The following diagram illustrates these relationships.
Energy Consumption
As the table below shows, frequency inverters allow you to consume less energy than other speed control techniques when load requirements are less than full speed, as is usually the case in HVAC applications.
Typical Energy Consumption of a Centrifugal Fan System Using Selected Speed Control Techniques
Tighter Process Control with inverters
No other AC motor control method compares to inverters when it comes to accurate process control. Full-voltage (across the line) starters can only run the motor at full speed, and soft starts and reduced voltage soft starters can only gradually ramp the motor up to full speed, and back down to shutdown. inverters, on the other hand, can be programmed to run the motor at a precise speed, to stop at a precise position, or to apply a specific amount of torque.
in fact, modern AC inverters are very close to the DC drive in terms of fast torque response and speed accuracy. However, AC motors are much more reliable and affordable than DC motors, making them far more prevalent.
Most inverters used in the field utilize Volts/Hertz type control, which means they provide open-loop operation. These inverters are unable to retrieve feedback from the process, but are sufficient for the majority of inverter applications. Many open-loop inverters do offer slip compensation though, which enables the inverter to measure its output current and estimate the difference in actual speed and the setpoint (the programmed input value). The inverter will then automatically adjust itself towards the setpoint based on this estimation.
Most variable torque inverters have PiD capability for fan and pump applications, which allows the inverter to hold the setpoint based on actual feedback from the process, rather than relying on an estimation. A transducer or transmitter is used to detect process variables such as pressure levels, liquid flow rate, air flow rate, or liquid level. Then the signal is sent to a PLC, which communicates the feedback from the process to the inverter. The inverter uses this continual feedback to adjust itself to hold the setpoint.
High levels of accuracy for other applications can also be achieved through inverters that offer closed-loop operation. Closed-loop operation can be accomplished with either a field-oriented vector inverter, or a sensorless vector inverter. The field-oriented vector inverter obtains process feedback from an encoder, which measures and transmits to the inverter the speed and/or rate of the process, such as a conveyor, machine tool, or extruder. The inverter then adjusts itself accordingly to sustain the programmed speed, rate, torque, and/or position.
Extended Equipment Life and Reduced Maintenance
Single-speed starting methods start motors abruptly, subjecting the motor to a high starting torque and to current surges that are up to 10 times the full-load current. inverters, on the other hand, gradually ramp the motor up to operating speed to lessen mechanical and electrical stress, reducing maintenance and repair costs, and extending the life of the motor and the driven equipment.
Soft starts, or reduced-voltage soft starters (RVSS), are also able to step a motor up gradually, but inverters can be programmed to ramp up the motor much more gradually and smoothly, and can operate the motor at less than full speed to decrease wear and tear. inverters can also run a motor in specialized patterns to further minimize mechanical and electrical stress. For example, an S-curve pattern can be applied to a conveyor application for smoother decel/accel control, which reduces the backlash that can occur when a conveyor is accelerating or decelerating.
Problems Caused by Full-Voltage Starters
At the instant of energization, the locked rotor (zero-speed) is about 600% of full-load running current This heavy current then drops off gradually as the load breaks loose, and the motor comes up to speed, but causes unacceptable voltage sag on the power system, adversely affecting other loads. it can also cause shock damage and long-term excessive wear on the motor. Using this starting method may force the utility to impose a limit on the size of motors you can use, since across-the-line starting causes problems upstream into the utility's system, creating problems for other customers. The switching surges of abruptly starting and stopping create stress on the motor insulation.